CVE-2022-28613NVD status: Modified

RTU500 series CMU Firmware: Improper Validation of Specified Quantity in Input

CVE-2022-28613 is a high-severity improper validation of specified quantity in input vulnerability in RTU500 series CMU Firmware from Hitachi Energy, with a CVSS 3.1 base score of 7.5 out of 10. It can be exploited remotely over the network by an unauthenticated attacker, without any action from a user. Affected RTU500 series CMU Firmware versions: 12.0.*; 12.2.*; 12.4.*, and others listed below. The record does not name a fixed version, so check the vendor advisory. There is no confirmed exploitation so far. EPSS estimates a 0.99% chance of exploitation within 30 days, higher than 63% of scored CVEs.

Next patch cycle

High severity with no evidence of exploitation so far.

What to do

  1. Update Rtu500 Firmware to 12.2.12.0 or a later version.
  2. Until you can update, restrict network access to the affected service so it is not reachable from untrusted networks.

Affected products and versions

VendorProductAffected versionsFixed in
Hitachi EnergyRTU500 series CMU Firmware12.0.*; 12.2.*; 12.4.*; 12.6.*; 12.7.*; 13.2.*Not stated
ABBRtu500 Firmware12.2.1.0 up to, but not including, 12.2.12.012.2.12.0

Version data comes from the organisation that assigned the CVE. Confirm against the vendor advisory before deciding you are unaffected.

How the severity score breaks down

Attack vector
NetworkCan be exploited remotely over a network, including the internet.
Attack complexity
LowNo special conditions are needed; the attack works reliably.
Privileges required
NoneNo account or login is needed.
User interaction
NoneNo action by a victim is required.
Scope
UnchangedImpact stays within the vulnerable component.
Confidentiality
NoneNo data is disclosed.
Integrity
NoneNothing can be modified.
Availability
HighThe component can be taken down completely.

Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H. Scored by NVD.

Scoring systemScoreSeverityScored by
CVSS 3.17.5HighCNA (hitachienergy.com)
CVSS 3.17.5HighNVD
CVSS 2.07.8HighNVD

Official description

A vulnerability exists in the HCI Modbus TCP function included in the product versions listed above. If the HCI Modbus TCP is en-abled and configured, an attacker could exploit the vulnerability by sending a specially crafted message to the RTU500, causing the receiving RTU500 CMU to reboot. The vulnerability is caused by the validation error in the length information carried in MBAP header in the HCI Modbus TCP function.

Source: the CVE record as published by its numbering authority, via NVD and CVE.org.

The underlying weakness: Improper Validation of Specified Quantity in Input

The product receives input that is expected to specify a quantity (such as size or length), but it does not validate or incorrectly validates that the quantity has the required properties.

More Improper Validation of Specified Quantity in Input vulnerabilities (CWE-1284)

Timeline

  1. CVE record published.
  2. Record last changed materially (score, affected products, status or references).

References

Other vulnerabilities in RTU500 series CMU Firmware

All RTU500 series CMU Firmware vulnerabilities

Recent Improper Validation of Specified Quantity in Input vulnerabilities

Spotted an error? Tell us.