CyberSecBulletin
CVE-2022-29922NVD status: Modified

Improper Input Validation vulnerability in the handling of a specially crafted IEC 61850…

CVE-2022-29922 is a high-severity improper input validation vulnerability in MicroSCADA X SYS600 from Hitachi Energy, with a CVSS 3.1 base score of 7.5 out of 10. It can be exploited remotely over the network by an unauthenticated attacker, without any action from a user. Affected MicroSCADA X SYS600 versions: 10; 10.1; 10.1.1, and others listed below. The record does not name a fixed version, so check the vendor advisory. There is no confirmed exploitation so far. EPSS estimates a 0.81% chance of exploitation within 30 days, higher than 57% of scored CVEs.

Next patch cycle

High severity with no evidence of exploitation so far.

What to do

  1. Check which version of MicroSCADA X SYS600 you run against the affected versions below, and install the vendor's latest release.
  2. Read the advisory on search.abb.com for workarounds and exact fixed builds.
  3. Until you can update, restrict network access to the affected service so it is not reachable from untrusted networks.

Affected products and versions

VendorProductAffected versionsFixed in
Hitachi EnergyMicroSCADA X SYS60010; 10.1; 10.1.1; 10.2; 10.2.1; 10.3; 10.3.1Not stated
Hitachi EnergyMicroSCADA Pro SYS6009.2 FP2 Hotfix 4 and earlierNot stated

Version data comes from the organisation that assigned the CVE. Confirm against the vendor advisory before deciding you are unaffected.

How the severity score breaks down

Attack vector
NetworkCan be exploited remotely over a network, including the internet.
Attack complexity
LowNo special conditions are needed; the attack works reliably.
Privileges required
NoneNo account or login is needed.
User interaction
NoneNo action by a victim is required.
Scope
UnchangedImpact stays within the vulnerable component.
Confidentiality
NoneNo data is disclosed.
Integrity
NoneNothing can be modified.
Availability
HighThe component can be taken down completely.

Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H. Scored by NVD.

Scoring systemScoreSeverityScored by
CVSS 3.17.5HighCNA (hitachienergy.com)
CVSS 3.17.5HighNVD

Official description

Improper Input Validation vulnerability in the handling of a specially crafted IEC 61850 packet with a valid data item but with incorrect data type in the IEC 61850 OPC Server in the Hitachi Energy MicroSCADA X SYS600, MicroSCADA Pro SYS600. The vulnerability may cause a denial-of-service on the IEC 61850 OPC Server part of the SYS600 product. This issue affects: Hitachi Energy MicroSCADA Pro SYS600 version 9.4 FP2 Hotfix 4 and earlier versions Hitachi Energy MicroSCADA X SYS600 version 10 to version 10.3.1. cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.0:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_pro_sys600:9.4:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.1.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.2.1:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3:*:*:*:*:*:*:* cpe:2.3:a:hitachienergy:microscada_x_sys600:10.3.1:*:*:*:*:*:*:*

Source: the CVE record as published by its numbering authority, via NVD and CVE.org.

The underlying weakness: Improper Input Validation

The product receives input or data, but it does not validate or incorrectly validates that the input has the properties that are required to process the data safely and correctly.

How developers prevent this class of flaw

  • Consider using language-theoretic security (LangSec) techniques that characterize inputs using a formal language and build recognizers for that language. This effectively requires parsing to be a distinct layer that effectively enforces a boundary between raw input and internal data representations, instead of allowing parser code to be scattered throughout the program, where it could be subject to errors or inconsistencies that create weaknesses.
  • Use an input validation framework such as Struts or the OWASP ESAPI Validation API. Note that using a framework does not automatically address all input validation problems; be mindful of weaknesses that could arise from misusing the framework itself (CWE-1173).
  • Understand all the potential areas where untrusted inputs can enter the product, including but not limited to: parameters or arguments, cookies, anything read from the network, environment variables, reverse DNS lookups, query results, request headers, URL components, e-mail, files, filenames, databases, and any external systems that provide data to the application. Remember that such inputs may be obtained indirectly through API calls.

More Improper Input Validation vulnerabilities (CWE-20)

Timeline

  1. CVE record published.
  2. CISA published its SSVC assessment (exploitation: none, automatable: yes, technical impact: partial).
  3. Record last changed materially (score, affected products, status or references).

References

Other vulnerabilities in MicroSCADA X SYS600

All MicroSCADA X SYS600 vulnerabilities

Recent Improper Input Validation vulnerabilities

Spotted an error? Tell us.