CyberSecBulletin
CVE-2022-3010NVD status: Modified

TopControl Suite - Bacnet: Use of Password Hash With Insufficient Computational Effort

CVE-2022-3010 is a high-severity use of password hash with insufficient computational effort vulnerability in TopControl Suite - Bacnet from Priva, with a CVSS 3.1 base score of 7.5 out of 10. It can be exploited remotely over the network by an unauthenticated attacker, without any action from a user. The record lists version 8.7.8.0 as the first without the flaw, so updating TopControl Suite - Bacnet to that release or later removes the exposure. There is no confirmed exploitation so far. EPSS estimates a 0.58% chance of exploitation within 30 days, which is low compared with other CVEs.

Next patch cycle

High severity with no evidence of exploitation so far.

What to do

  1. Update TopControl Suite - Bacnet to 8.7.8.0 or a later version.
  2. Update TopControl Suite - Blue ID to 8.7.8.0 or a later version.
  3. Update TopControl Suite - Compass to 8.7.8.0 or a later version.
  4. Until you can update, restrict network access to the affected service so it is not reachable from untrusted networks.

Affected products and versions

VendorProductAffected versionsFixed in
PrivaTopControl Suite - BacnetAll versions prior to 8.7.8.0 up to, but not including, 8.7.8.08.7.8.0
PrivaTopControl Suite - Blue IDAll versions prior to 8.7.8.0 up to, but not including, 8.7.8.08.7.8.0
PrivaTopControl Suite - CompassAll versions prior to 8.7.8.0 up to, but not including, 8.7.8.08.7.8.0
PrivaTopControl Suite - ConnectAll versions prior to 8.7.8.0 up to, but not including, 8.7.8.08.7.8.0
PrivaTopControl Suite - TPCAll versions prior to 8.7.8.0 up to, but not including, 8.7.8.08.7.8.0
PrivaTop Control Suite8.7.8.0 and earlierNot stated

Version data comes from the organisation that assigned the CVE. Confirm against the vendor advisory before deciding you are unaffected.

How the severity score breaks down

Attack vector
NetworkCan be exploited remotely over a network, including the internet.
Attack complexity
LowNo special conditions are needed; the attack works reliably.
Privileges required
NoneNo account or login is needed.
User interaction
NoneNo action by a victim is required.
Scope
UnchangedImpact stays within the vulnerable component.
Confidentiality
HighAll data handled by the component can be read.
Integrity
NoneNothing can be modified.
Availability
NoneAvailability is not affected.

Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N. Scored by NVD.

Scoring systemScoreSeverityScored by
CVSS 3.17.5HighCNA (divd.nl)
CVSS 3.17.5HighNVD

Official description

The Priva TopControl Suite contains predictable credentials for the SSH service, based on the Serial number. Which makes it possible for an attacker to calculate the login credentials for the Priva TopControll suite.

Source: the CVE record as published by its numbering authority, via NVD and CVE.org.

The underlying weakness: Use of Password Hash With Insufficient Computational Effort

The product generates a hash for a password, but it uses a scheme that does not provide a sufficient level of computational effort that would make password cracking attacks infeasible or expensive.

How developers prevent this class of flaw

  • When using industry-approved techniques, use them correctly. Don't cut corners by skipping resource-intensive steps (CWE-325). These steps are often essential for preventing common attacks.

More Use of Password Hash With Insufficient Computational Effort vulnerabilities (CWE-916)

Timeline

  1. CVE record published.
  2. CISA published its SSVC assessment (exploitation: none, automatable: yes, technical impact: partial).
  3. Record last changed materially (score, affected products, status or references).

References

Third-party and government advisories

Recent Use of Password Hash With Insufficient Computational Effort vulnerabilities

Spotted an error? Tell us.