SIMATIC CP 1242-7 V2: Deadlock
CVE-2022-43767 is a high-severity deadlock vulnerability in SIMATIC CP 1242-7 V2 from Siemens, with a CVSS 3.1 base score of 7.5 out of 10. It can be exploited remotely over the network by an unauthenticated attacker, without any action from a user. The record lists version V3.4.29 as the first without the flaw, so updating SIMATIC CP 1242-7 V2 to that release or later removes the exposure. There is no confirmed exploitation so far. EPSS estimates a 0.72% chance of exploitation within 30 days, higher than 55% of scored CVEs.
High severity with no evidence of exploitation so far.
What to do
- Update SIMATIC CP 1242-7 V2 to V3.4.29 or a later version.
- Update SIMATIC CP 1243-1 to V3.4.29 or a later version.
- Update SIMATIC CP 1243-1 DNP3 (incl. SIPLUS variants) to V3.4.29 or a later version.
- Read the advisory on cert-portal.siemens.com for workarounds and exact fixed builds.
- Until you can update, restrict network access to the affected service so it is not reachable from untrusted networks.
Affected products and versions
| Vendor | Product | Affected versions | Fixed in |
|---|---|---|---|
| Siemens | SIMATIC CP 1242-7 V2 | before V3.4.29; all versions | V3.4.29 |
| Siemens | SIMATIC CP 1243-1 | before V3.4.29; all versions | V3.4.29 |
| Siemens | SIMATIC CP 1243-1 DNP3 (incl. SIPLUS variants) | before V3.4.29 | V3.4.29 |
| Siemens | SIMATIC CP 1243-1 IEC (incl. SIPLUS variants) | before V3.4.29 | V3.4.29 |
| Siemens | SIMATIC CP 1243-7 LTE EU | before V3.4.29; all versions | V3.4.29 |
| Siemens | SIMATIC CP 1243-7 LTE US | before V3.4.29; all versions | V3.4.29 |
| Siemens | SIMATIC CP 1243-8 IRC | before V3.4.29; all versions | V3.4.29 |
| Siemens | SIMATIC CP 1542SP-1 | before V2.3; before 2.3 | V2.3, 2.3 |
| Siemens | SIMATIC CP 1542SP-1 IRC | before V2.3; before 2.3 | V2.3, 2.3 |
| Siemens | SIMATIC CP 1543SP-1 | before V2.3; before 2.3 | V2.3, 2.3 |
| Siemens | SIMATIC CP 443-1 | before V3.3; before 3.3 | V3.3, 3.3 |
| Siemens | SIMATIC CP 443-1 Advanced | before V3.3; before 3.3 | V3.3, 3.3 |
| Siemens | SIPLUS ET 200SP CP 1542SP-1 IRC TX RAIL | before V2.3; before 2.3 | V2.3, 2.3 |
| Siemens | SIPLUS ET 200SP CP 1543SP-1 ISEC | before V2.3; before 2.3 | V2.3, 2.3 |
| Siemens | SIPLUS ET 200SP CP 1543SP-1 ISEC TX RAIL | before V2.3; before 2.3 | V2.3, 2.3 |
| Siemens | SIPLUS NET CP 1242-7 V2 | before V3.4.29; all versions | V3.4.29 |
| Siemens | SIPLUS NET CP 443-1 | before V3.3; before 3.3 | V3.3, 3.3 |
| Siemens | SIPLUS NET CP 443-1 Advanced | before V3.3; before 3.3 | V3.3, 3.3 |
| Siemens | SIPLUS S7-1200 CP 1243-1 | before V3.4.29; all versions | V3.4.29 |
| Siemens | SIPLUS S7-1200 CP 1243-1 RAIL | before V3.4.29; all versions | V3.4.29 |
| Siemens | SIPLUS TIM 1531 IRC | before V2.3.6; before 2.3.6 | V2.3.6, 2.3.6 |
| Siemens | TIM 1531 IRC | before V2.3.6; before 2.3.6 | V2.3.6, 2.3.6 |
| Siemens | simatic_cp_1243-1_dnp3 | all versions | Not stated |
| Siemens | simatic_cp_1243-1_iec | all versions | Not stated |
| Siemens | Simatic Cp 1242-7 V2 Firmware | Not specified in the record | Not stated |
Version data comes from the organisation that assigned the CVE; 23 further products are omitted here. Confirm against the vendor advisory before deciding you are unaffected.
How the severity score breaks down
- Attack vector
- NetworkCan be exploited remotely over a network, including the internet.
- Attack complexity
- LowNo special conditions are needed; the attack works reliably.
- Privileges required
- NoneNo account or login is needed.
- User interaction
- NoneNo action by a victim is required.
- Scope
- UnchangedImpact stays within the vulnerable component.
- Confidentiality
- NoneNo data is disclosed.
- Integrity
- NoneNothing can be modified.
- Availability
- HighThe component can be taken down completely.
Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H. Scored by CNA (siemens.com).
Official description
A vulnerability has been identified in SIMATIC CP 1242-7 V2 (6GK7242-7KX31-0XE0) (All versions < V3.4.29), SIMATIC CP 1243-1 (6GK7243-1BX30-0XE0) (All versions < V3.4.29), SIMATIC CP 1243-1 DNP3 (incl. SIPLUS variants) (All versions < V3.4.29), SIMATIC CP 1243-1 IEC (incl. SIPLUS variants) (All versions < V3.4.29), SIMATIC CP 1243-7 LTE EU (6GK7243-7KX30-0XE0) (All versions < V3.4.29), SIMATIC CP 1243-7 LTE US (6GK7243-7SX30-0XE0) (All versions < V3.4.29), SIMATIC CP 1243-8 IRC (6GK7243-8RX30-0XE0) (All versions < V3.4.29), SIMATIC CP 1542SP-1 (6GK7542-6UX00-0XE0) (All versions < V2.3), SIMATIC CP 1542SP-1 IRC (6GK7542-6VX00-0XE0) (All versions < V2.3), SIMATIC CP 1543SP-1 (6GK7543-6WX00-0XE0) (All versions < V2.3), SIMATIC CP 443-1 (6GK7443-1EX30-0XE0) (All versions < V3.3), SIMATIC CP 443-1 (6GK7443-1EX30-0XE1) (All versions < V3.3), SIMATIC CP 443-1 Advanced (6GK7443-1GX30-0XE0) (All versions < V3.3), SIPLUS ET 200SP CP 1542SP-1 IRC TX RAIL (6AG2542-6VX00-4XE0) (All versions < V2.3), SIPLUS ET 200SP CP 1543SP-1 ISEC (6AG1543-6WX00-7XE0) (All versions < V2.3), SIPLUS ET 200SP CP 1543SP-1 ISEC TX RAIL (6AG2543-6WX00-4XE0) (All versions < V2.3), SIPLUS NET CP 1242-7 V2 (6AG1242-7KX31-7XE0) (All versions < V3.4.29), SIPLUS NET CP 443-1 (6AG1443-1EX30-4XE0) (All versions < V3.3), SIPLUS NET CP 443-1 Advanced (6AG1443-1GX30-4XE0) (All versions < V3.3), SIPLUS S7-1200 CP 1243-1 (6AG1243-1BX30-2AX0) (All versions < V3.4.29), SIPLUS S7-1200 CP 1243-1 RAIL (6AG2243-1BX30-1XE0) (All versions < V3.4.29), SIPLUS TIM 1531 IRC (6AG1543-1MX00-7XE0) (All versions < V2.3.6), TIM 1531 IRC (6GK7543-1MX00-0XE0) (All versions < V2.3.6). The webserver of the affected products contains a vulnerability that may lead to a denial of service condition. An attacker may cause a denial of service situation of the webserver of the affected product.
Source: the CVE record as published by its numbering authority, via NVD and CVE.org.
The underlying weakness: Deadlock
The product contains multiple threads or executable segments that are waiting for each other to release a necessary lock, resulting in deadlock.
Timeline
- CVE record published.
- CISA published its SSVC assessment (exploitation: none, automatable: yes, technical impact: partial).