CyberSecBulletin
CVE-2023-39463NVD status: Analyzed

SCADA Data Gateway: Unrestricted Upload of File with Dangerous Type

CVE-2023-39463 is a high-severity unrestricted upload of file with dangerous type vulnerability in SCADA Data Gateway from Triangle MicroWorks, with a CVSS 3.0 base score of 7.2 out of 10. It can be exploited remotely over the network by an attacker with administrator privileges, without any action from a user. Affected SCADA Data Gateway versions: 5.1.3.20324. The record does not name a fixed version, so check the vendor advisory. There is no confirmed exploitation so far. EPSS estimates a 1.24% chance of exploitation within 30 days, higher than 70% of scored CVEs.

Next patch cycle

High severity with no evidence of exploitation so far.

What to do

  1. Check which version of SCADA Data Gateway you run against the affected versions below, and install the vendor's latest release.

Affected products and versions

VendorProductAffected versionsFixed in
Triangle MicroWorksSCADA Data Gateway5.1.3.20324Not stated
Trianglemicroworksscada_data_gateway5.1.3.20324Not stated

Version data comes from the organisation that assigned the CVE. Confirm against the vendor advisory before deciding you are unaffected.

How the severity score breaks down

Attack vector
NetworkCan be exploited remotely over a network, including the internet.
Attack complexity
LowNo special conditions are needed; the attack works reliably.
Privileges required
HighAdministrator-level access is required first.
User interaction
NoneNo action by a victim is required.
Scope
UnchangedImpact stays within the vulnerable component.
Confidentiality
HighAll data handled by the component can be read.
Integrity
HighData or code can be modified at will.
Availability
HighThe component can be taken down completely.

Vector: CVSS:3.0/AV:N/AC:L/PR:H/UI:N/S:U/C:H/I:H/A:H. Scored by CNA (trendmicro.com).

Official description

Triangle MicroWorks SCADA Data Gateway Trusted Certification Unrestricted Upload of File Remote Code Execution Vulnerability. This vulnerability allows remote attackers to execute arbitrary code on affected installations of Triangle MicroWorks SCADA Data Gateway. Although authentication is required to exploit this vulnerability, the existing authentication mechanism can be bypassed. The specific flaw exists within the trusted certification feature. The issue lies in the handling of the OpcUaSecurityCertificateAuthorityTrustDir variable, which allows an arbitrary file write with attacker-controlled data. An attacker can leverage this vulnerability to execute code in the context of SYSTEM. Was ZDI-CAN-20537.

Source: the CVE record as published by its numbering authority, via NVD and CVE.org.

The underlying weakness: Unrestricted Upload of File with Dangerous Type

The product allows the upload or transfer of dangerous file types that are automatically processed within its environment.

How developers prevent this class of flaw

  • Generate a new, unique filename for an uploaded file instead of using the user-supplied filename, so that no external input is used at all.
  • When the set of acceptable objects, such as filenames or URLs, is limited or known, create a mapping from a set of fixed input values (such as numeric IDs) to the actual filenames or URLs, and reject all other inputs.
  • Consider storing the uploaded files outside of the web document root entirely. Then, use other mechanisms to deliver the files dynamically.

More Unrestricted Upload of File with Dangerous Type vulnerabilities (CWE-434)

Timeline

  1. CVE record published.
  2. CISA published its SSVC assessment (exploitation: none, automatable: no, technical impact: total).
  3. Record last changed materially (score, affected products, status or references).

References

Third-party and government advisories

Other vulnerabilities in SCADA Data Gateway

All SCADA Data Gateway vulnerabilities

Recent Unrestricted Upload of File with Dangerous Type vulnerabilities