CyberSecBulletin
CVE-2024-22040NVD status: Deferred

Cerberus PRO EN Engineering Tool: Out-of-bounds Read

CVE-2024-22040 is a high-severity out-of-bounds read vulnerability in Cerberus PRO EN Engineering Tool from Siemens, with a CVSS 3.1 base score of 7.5 out of 10. It can be exploited remotely over the network by an unauthenticated attacker, without any action from a user. Affected Cerberus PRO EN Engineering Tool versions: all versions. The record does not name a fixed version, so check the vendor advisory. There is no confirmed exploitation so far. EPSS estimates a 0.83% chance of exploitation within 30 days, higher than 58% of scored CVEs.

Next patch cycle

High severity with no evidence of exploitation so far.

What to do

  1. Update Cerberus PRO EN Fire Panel FC72x IP8 to IP8 SR4 or a later version.
  2. Update Cerberus PRO EN X200 Cloud Distribution IP8 to V4.3.5618 or a later version.
  3. Update Cerberus PRO EN X300 Cloud Distribution IP8 to V4.3.5617 or a later version.
  4. Until you can update, restrict network access to the affected service so it is not reachable from untrusted networks.

Affected products and versions

VendorProductAffected versionsFixed in
SiemensCerberus PRO EN Engineering Toolall versionsNot stated
SiemensCerberus PRO EN Fire Panel FC72x IP6all versionsNot stated
SiemensCerberus PRO EN Fire Panel FC72x IP7all versionsNot stated
SiemensCerberus PRO EN Fire Panel FC72x IP8before IP8 SR4IP8 SR4
SiemensCerberus PRO EN X200 Cloud Distribution IP7all versionsNot stated
SiemensCerberus PRO EN X200 Cloud Distribution IP8before V4.3.5618V4.3.5618
SiemensCerberus PRO EN X300 Cloud Distribution IP7all versionsNot stated
SiemensCerberus PRO EN X300 Cloud Distribution IP8before V4.3.5617V4.3.5617
SiemensCerberus PRO UL Compact Panel FC922/924before MP4MP4
SiemensCerberus PRO UL Engineering Toolbefore MP4MP4
SiemensCerberus PRO UL X300 Cloud Distributionbefore V4.3.0001V4.3.0001
SiemensDesigo Fire Safety UL Compact Panel FC2025/2050before MP4MP4
SiemensDesigo Fire Safety UL Engineering Toolbefore MP4; before v4.3.0001MP4, v4.3.0001
SiemensDesigo Fire Safety UL X300 Cloud Distributionbefore V4.3.0001V4.3.0001
SiemensSinteso FS20 EN Engineering Toolall versionsNot stated
SiemensSinteso FS20 EN Fire Panel FC20 MP6all versionsNot stated
SiemensSinteso FS20 EN Fire Panel FC20 MP7all versionsNot stated
SiemensSinteso FS20 EN Fire Panel FC20 MP8before MP8 SR4MP8 SR4
SiemensSinteso FS20 EN X200 Cloud Distribution MP7all versionsNot stated
SiemensSinteso FS20 EN X200 Cloud Distribution MP8before V4.3.5618V4.3.5618
SiemensSinteso FS20 EN X300 Cloud Distribution MP7all versionsNot stated
SiemensSinteso FS20 EN X300 Cloud Distribution MP8before V4.3.5617V4.3.5617
SiemensSinteso Mobileall versionsNot stated
Siemenscerberus_pro_en_fire_panel_fc72xNot specified in the recordNot stated
Siemenscerberus_pro_en_x300_cloud_distributionNot specified in the recordNot stated

Version data comes from the organisation that assigned the CVE; 7 further products are omitted here. Confirm against the vendor advisory before deciding you are unaffected.

How the severity score breaks down

Attack vector
NetworkCan be exploited remotely over a network, including the internet.
Attack complexity
LowNo special conditions are needed; the attack works reliably.
Privileges required
NoneNo account or login is needed.
User interaction
NoneNo action by a victim is required.
Scope
UnchangedImpact stays within the vulnerable component.
Confidentiality
NoneNo data is disclosed.
Integrity
NoneNothing can be modified.
Availability
HighThe component can be taken down completely.

Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H. Scored by CNA (siemens.com).

Official description

A vulnerability has been identified in Cerberus PRO EN Engineering Tool (All versions), Cerberus PRO EN Fire Panel FC72x IP6 (All versions), Cerberus PRO EN Fire Panel FC72x IP7 (All versions), Cerberus PRO EN Fire Panel FC72x IP8 (All versions < IP8 SR4), Cerberus PRO EN X200 Cloud Distribution IP7 (All versions), Cerberus PRO EN X200 Cloud Distribution IP8 (All versions < V4.3.5618), Cerberus PRO EN X300 Cloud Distribution IP7 (All versions), Cerberus PRO EN X300 Cloud Distribution IP8 (All versions < V4.3.5617), Cerberus PRO UL Compact Panel FC922/924 (All versions < MP4), Cerberus PRO UL Engineering Tool (All versions < MP4), Cerberus PRO UL X300 Cloud Distribution (All versions < V4.3.0001), Desigo Fire Safety UL Compact Panel FC2025/2050 (All versions < MP4), Desigo Fire Safety UL Engineering Tool (All versions < MP4), Desigo Fire Safety UL X300 Cloud Distribution (All versions < V4.3.0001), Sinteso FS20 EN Engineering Tool (All versions), Sinteso FS20 EN Fire Panel FC20 MP6 (All versions), Sinteso FS20 EN Fire Panel FC20 MP7 (All versions), Sinteso FS20 EN Fire Panel FC20 MP8 (All versions < MP8 SR4), Sinteso FS20 EN X200 Cloud Distribution MP7 (All versions), Sinteso FS20 EN X200 Cloud Distribution MP8 (All versions < V4.3.5618), Sinteso FS20 EN X300 Cloud Distribution MP7 (All versions), Sinteso FS20 EN X300 Cloud Distribution MP8 (All versions < V4.3.5617), Sinteso Mobile (All versions). The network communication library in affected systems insufficiently validates HMAC values which might result in a buffer overread. This could allow an unauthenticated remote attacker to crash the network service.

Source: the CVE record as published by its numbering authority, via NVD and CVE.org.

The underlying weakness: Out-of-bounds Read

The product reads data past the end, or before the beginning, of the intended buffer.

How developers prevent this class of flaw

  • Use a language that provides appropriate memory abstractions.

More Out-of-bounds Read vulnerabilities (CWE-125)

Timeline

  1. CVE record published.
  2. CISA published its SSVC assessment (exploitation: none, automatable: yes, technical impact: total).
  3. Record last changed materially (score, affected products, status or references).

References

Other vulnerabilities in Cerberus PRO EN Engineering Tool

All Cerberus PRO EN Engineering Tool vulnerabilities

Recent Out-of-bounds Read vulnerabilities

Spotted an error? Tell us.