CyberSecBulletin
CVE-2024-37367NVD status: Modified

FactoryTalk® View SE: Improper Authentication

CVE-2024-37367 is a high-severity improper authentication vulnerability in FactoryTalk® View SE from Rockwell Automation, with a CVSS 3.1 base score of 7.5 out of 10. It can be exploited remotely over the network by an unauthenticated attacker, without any action from a user. Affected FactoryTalk® View SE versions: v12. The record does not name a fixed version, so check the vendor advisory. There is no confirmed exploitation so far. EPSS estimates a 0.5% chance of exploitation within 30 days, which is low compared with other CVEs.

Next patch cycle

High severity with no evidence of exploitation so far.

What to do

  1. Update Factorytalk View to 14.0 or a later version.
  2. Until you can update, restrict network access to the affected service so it is not reachable from untrusted networks.

Affected products and versions

VendorProductAffected versionsFixed in
Rockwell AutomationFactoryTalk® View SEv12Not stated
Rockwell AutomationFactorytalk View12.0 up to, but not including, 14.014.0

Version data comes from the organisation that assigned the CVE. Confirm against the vendor advisory before deciding you are unaffected.

How the severity score breaks down

Attack vector
NetworkCan be exploited remotely over a network, including the internet.
Attack complexity
LowNo special conditions are needed; the attack works reliably.
Privileges required
NoneNo account or login is needed.
User interaction
NoneNo action by a victim is required.
Scope
UnchangedImpact stays within the vulnerable component.
Confidentiality
HighAll data handled by the component can be read.
Integrity
NoneNothing can be modified.
Availability
NoneAvailability is not affected.

Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N. Scored by NVD.

Scoring systemScoreSeverityScored by
CVSS 4.08.2HighCNA (rockwellautomation.com)
CVSS 3.17.5HighNVD

Official description

A user authentication vulnerability exists in the Rockwell Automation FactoryTalk® View SE v12. The vulnerability allows a user from a remote system with FTView to send a packet to the customer’s server to view an HMI project. This action is allowed without proper authentication verification.

Source: the CVE record as published by its numbering authority, via NVD and CVE.org.

The underlying weakness: Improper Authentication

When an actor claims to have a given identity, the product does not prove or insufficiently proves that the claim is correct.

How developers prevent this class of flaw

  • Use an authentication framework or library such as the OWASP ESAPI Authentication feature.

More Improper Authentication vulnerabilities (CWE-287)

Timeline

  1. CVE record published.
  2. CISA published its SSVC assessment (exploitation: none, automatable: no, technical impact: partial).
  3. Record last changed materially (score, affected products, status or references).

Other vulnerabilities in FactoryTalk® View SE

All FactoryTalk® View SE vulnerabilities

Recent Improper Authentication vulnerabilities

Spotted an error? Tell us.