CyberSecBulletin
CVE-2024-45386NVD status: Deferred

A vulnerability has been identified in SIMATIC PCS neo V4.0 (All versions), SIMATIC PCS neo…

CVE-2024-45386 is a high-severity vulnerability in SIMATIC PCS neo V4.0 from Siemens, with a CVSS 3.1 base score of 8.8 out of 10. It can be exploited remotely over the network by an unauthenticated attacker, but only if a user takes part, for example by opening a link or file. Affected SIMATIC PCS neo V4.0 versions: all versions. The record does not name a fixed version, so check the vendor advisory. There is no confirmed exploitation so far. EPSS estimates a 0.56% chance of exploitation within 30 days, which is low compared with other CVEs.

Next patch cycle

High severity with no evidence of exploitation so far.

What to do

  1. Update SIMATIC PCS neo V4.1 to V4.1 Update 2 or a later version.
  2. Update SIMATIC PCS neo V5.0 to V5.0 Update 1 or a later version.
  3. Update SIMOCODE ES V19 to V19 Update 1 or a later version.
  4. Until you can update, restrict network access to the affected service so it is not reachable from untrusted networks.
  5. Because the attack needs a user to take part, warn users about unexpected links and files related to this product until it is patched.

Affected products and versions

VendorProductAffected versionsFixed in
SiemensSIMATIC PCS neo V4.0all versionsNot stated
SiemensSIMATIC PCS neo V4.1before V4.1 Update 2V4.1 Update 2
SiemensSIMATIC PCS neo V5.0before V5.0 Update 1V5.0 Update 1
SiemensSIMOCODE ES V19before V19 Update 1V19 Update 1
SiemensSIRIUS Safety ES V19 (TIA Portal)before V19 Update 1V19 Update 1
SiemensSIRIUS Soft Starter ES V19 (TIA Portal)before V19 Update 1V19 Update 1
SiemensTIA Administratorbefore V3.0.4V3.0.4

Version data comes from the organisation that assigned the CVE. Confirm against the vendor advisory before deciding you are unaffected.

How the severity score breaks down

Attack vector
NetworkCan be exploited remotely over a network, including the internet.
Attack complexity
LowNo special conditions are needed; the attack works reliably.
Privileges required
NoneNo account or login is needed.
User interaction
RequiredA user must take an action such as opening a file or link.
Scope
UnchangedImpact stays within the vulnerable component.
Confidentiality
HighAll data handled by the component can be read.
Integrity
HighData or code can be modified at will.
Availability
HighThe component can be taken down completely.

Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:R/S:U/C:H/I:H/A:H. Scored by CNA (siemens.com).

Scoring systemScoreSeverityScored by
CVSS 4.08.7HighCNA (siemens.com)
CVSS 3.18.8HighCNA (siemens.com)

Official description

A vulnerability has been identified in SIMATIC PCS neo V4.0 (All versions), SIMATIC PCS neo V4.1 (All versions < V4.1 Update 2), SIMATIC PCS neo V5.0 (All versions < V5.0 Update 1), SIMOCODE ES V19 (All versions < V19 Update 1), SIRIUS Safety ES V19 (TIA Portal) (All versions < V19 Update 1), SIRIUS Soft Starter ES V19 (TIA Portal) (All versions < V19 Update 1), TIA Administrator (All versions < V3.0.4). Affected products do not correctly invalidate user sessions upon user logout. This could allow a remote unauthenticated attacker, who has obtained the session token by other means, to re-use a legitimate user's session even after logout.

Source: the CVE record as published by its numbering authority, via NVD and CVE.org.

Timeline

  1. CVE record published.
  2. CISA published its SSVC assessment (exploitation: none, automatable: no, technical impact: total).
  3. Record last changed materially (score, affected products, status or references).

References

Other vulnerabilities in SIMATIC PCS neo V4.0

All SIMATIC PCS neo V4.0 vulnerabilities

Spotted an error? Tell us.