CyberSecBulletin
CVE-2024-47943NVD status: Deferred

IoT Interface & CMC III Processing Unit: Improper Verification of Cryptographic Signature

CVE-2024-47943 is a critical-severity improper verification of cryptographic signature vulnerability in IoT Interface & CMC III Processing Unit from RITTAL GmbH & Co. KG, with a CVSS 3.1 base score of 9.8 out of 10. It can be exploited remotely over the network by an unauthenticated attacker, without any action from a user. Affected IoT Interface & CMC III Processing Unit versions: <6.21.00.2. The record does not name a fixed version, so check the vendor advisory. There is no confirmed exploitation so far. EPSS estimates a 0.64% chance of exploitation within 30 days, higher than 51% of scored CVEs.

Patch this week

Critical severity: a successful attack would have severe impact.

What to do

  1. Check which version of IoT Interface & CMC III Processing Unit you run against the affected versions below, and install the vendor's latest release.
  2. Until you can update, restrict network access to the affected service so it is not reachable from untrusted networks.

Affected products and versions

VendorProductAffected versionsFixed in
RITTAL GmbH & Co. KGIoT Interface & CMC III Processing Unit<6.21.00.2Not stated

Version data comes from the organisation that assigned the CVE. Confirm against the vendor advisory before deciding you are unaffected.

How the severity score breaks down

Attack vector
NetworkCan be exploited remotely over a network, including the internet.
Attack complexity
LowNo special conditions are needed; the attack works reliably.
Privileges required
NoneNo account or login is needed.
User interaction
NoneNo action by a victim is required.
Scope
UnchangedImpact stays within the vulnerable component.
Confidentiality
HighAll data handled by the component can be read.
Integrity
HighData or code can be modified at will.
Availability
HighThe component can be taken down completely.

Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H. Scored by CISA (ADP).

Official description

The firmware upgrade function in the admin web interface of the Rittal IoT Interface & CMC III Processing Unit devices checks if the patch files are signed before executing the containing run.sh script. The signing process is kind of an HMAC with a long string as key which is hard-coded in the firmware and is freely available for download. This allows crafting malicious "signed" .patch files in order to compromise the device and execute arbitrary code.

Source: the CVE record as published by its numbering authority, via NVD and CVE.org.

The underlying weakness: Improper Verification of Cryptographic Signature

The product does not verify, or incorrectly verifies, the cryptographic signature for data.

More Improper Verification of Cryptographic Signature vulnerabilities (CWE-347)

Timeline

  1. CVE record published.
  2. CISA published its SSVC assessment (exploitation: poc, automatable: yes, technical impact: total).
  3. Record last changed materially (score, affected products, status or references).

References

Other vulnerabilities in IoT Interface & CMC III Processing Unit

All IoT Interface & CMC III Processing Unit vulnerabilities

Recent Improper Verification of Cryptographic Signature vulnerabilities

Spotted an error? Tell us.