RTU500: Missing Synchronization
CVE-2025-1445 is a high-severity missing synchronization vulnerability in RTU500 from Hitachi Energy, with a CVSS 3.1 base score of 7.5 out of 10. It can be exploited remotely over the network by an unauthenticated attacker, without any action from a user. Affected RTU500 versions: 13.7.1 through 13.7.4. The record does not name a fixed version, so check the vendor advisory. There is no confirmed exploitation so far. EPSS estimates a 0.34% chance of exploitation within 30 days, which is low compared with other CVEs.
High severity with no evidence of exploitation so far.
What to do
- Check which version of RTU500 you run against the affected versions below, and install the vendor's latest release.
- Until you can update, restrict network access to the affected service so it is not reachable from untrusted networks.
Affected products and versions
| Vendor | Product | Affected versions | Fixed in |
|---|---|---|---|
| Hitachi Energy | RTU500 | 13.7.1 through 13.7.4 | Not stated |
Version data comes from the organisation that assigned the CVE. Confirm against the vendor advisory before deciding you are unaffected.
How the severity score breaks down
- Attack vector
- NetworkCan be exploited remotely over a network, including the internet.
- Attack complexity
- LowNo special conditions are needed; the attack works reliably.
- Privileges required
- NoneNo account or login is needed.
- User interaction
- NoneNo action by a victim is required.
- Scope
- UnchangedImpact stays within the vulnerable component.
- Confidentiality
- NoneNo data is disclosed.
- Integrity
- NoneNothing can be modified.
- Availability
- HighThe component can be taken down completely.
Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H. Scored by CNA (hitachienergy.com).
| Scoring system | Score | Severity | Scored by |
|---|---|---|---|
| CVSS 4.0 | 8.7 | High | CNA (hitachienergy.com) |
| CVSS 3.1 | 7.5 | High | CNA (hitachienergy.com) |
Official description
A vulnerability exists in RTU IEC 61850 client and server functionality that could impact the availability if renegotiation of an open IEC61850 TLS connection takes place in specific timing situations, when IEC61850 communication is active. Precondition is that IEC61850 as client or server are configured using TLS on RTU500 device. It affects the CMU the IEC61850 stack is configured on.
Source: the CVE record as published by its numbering authority, via NVD and CVE.org.
The underlying weakness: Missing Synchronization
The product utilizes a shared resource in a concurrent manner but does not attempt to synchronize access to the resource.
Timeline
- CVE record published.
- CISA published its SSVC assessment (exploitation: none, automatable: yes, technical impact: partial).
- Record last changed materially (score, affected products, status or references).
References