CyberSecBulletin
CVE-2025-1445NVD status: Deferred

RTU500: Missing Synchronization

CVE-2025-1445 is a high-severity missing synchronization vulnerability in RTU500 from Hitachi Energy, with a CVSS 3.1 base score of 7.5 out of 10. It can be exploited remotely over the network by an unauthenticated attacker, without any action from a user. Affected RTU500 versions: 13.7.1 through 13.7.4. The record does not name a fixed version, so check the vendor advisory. There is no confirmed exploitation so far. EPSS estimates a 0.34% chance of exploitation within 30 days, which is low compared with other CVEs.

Next patch cycle

High severity with no evidence of exploitation so far.

What to do

  1. Check which version of RTU500 you run against the affected versions below, and install the vendor's latest release.
  2. Until you can update, restrict network access to the affected service so it is not reachable from untrusted networks.

Affected products and versions

VendorProductAffected versionsFixed in
Hitachi EnergyRTU50013.7.1 through 13.7.4Not stated

Version data comes from the organisation that assigned the CVE. Confirm against the vendor advisory before deciding you are unaffected.

How the severity score breaks down

Attack vector
NetworkCan be exploited remotely over a network, including the internet.
Attack complexity
LowNo special conditions are needed; the attack works reliably.
Privileges required
NoneNo account or login is needed.
User interaction
NoneNo action by a victim is required.
Scope
UnchangedImpact stays within the vulnerable component.
Confidentiality
NoneNo data is disclosed.
Integrity
NoneNothing can be modified.
Availability
HighThe component can be taken down completely.

Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H. Scored by CNA (hitachienergy.com).

Scoring systemScoreSeverityScored by
CVSS 4.08.7HighCNA (hitachienergy.com)
CVSS 3.17.5HighCNA (hitachienergy.com)

Official description

A vulnerability exists in RTU IEC 61850 client and server functionality that could impact the availability if renegotiation of an open IEC61850 TLS connection takes place in specific timing situations, when IEC61850 communication is active. Precondition is that IEC61850 as client or server are configured using TLS on RTU500 device. It affects the CMU the IEC61850 stack is configured on.

Source: the CVE record as published by its numbering authority, via NVD and CVE.org.

The underlying weakness: Missing Synchronization

The product utilizes a shared resource in a concurrent manner but does not attempt to synchronize access to the resource.

More Missing Synchronization vulnerabilities (CWE-820)

Timeline

  1. CVE record published.
  2. CISA published its SSVC assessment (exploitation: none, automatable: yes, technical impact: partial).
  3. Record last changed materially (score, affected products, status or references).

References

Other vulnerabilities in RTU500

All RTU500 vulnerabilities

Spotted an error? Tell us.