CyberSecBulletin
CVE-2025-7972NVD status: Analyzed

FactoryTalk® Linx: Incorrect User Management

CVE-2025-7972 is a critical-severity incorrect user management vulnerability in FactoryTalk® Linx from Rockwell Automation, with a CVSS 3.1 base score of 9.1 out of 10. It can be exploited remotely over the network by an unauthenticated attacker, without any action from a user. Affected FactoryTalk® Linx versions: All prior to 6.50. The record does not name a fixed version, so check the vendor advisory. There is no confirmed exploitation so far. EPSS estimates a 0.53% chance of exploitation within 30 days, which is low compared with other CVEs.

Patch this week

Critical severity: a successful attack would have severe impact.

What to do

  1. Check which version of FactoryTalk® Linx you run against the affected versions below, and install the vendor's latest release.
  2. Read the advisory on rockwellautomation.com for workarounds and exact fixed builds.
  3. Until you can update, restrict network access to the affected service so it is not reachable from untrusted networks.

Affected products and versions

VendorProductAffected versionsFixed in
Rockwell AutomationFactoryTalk® LinxAll prior to 6.50Not stated

Version data comes from the organisation that assigned the CVE. Confirm against the vendor advisory before deciding you are unaffected.

How the severity score breaks down

Attack vector
NetworkCan be exploited remotely over a network, including the internet.
Attack complexity
LowNo special conditions are needed; the attack works reliably.
Privileges required
NoneNo account or login is needed.
User interaction
NoneNo action by a victim is required.
Scope
UnchangedImpact stays within the vulnerable component.
Confidentiality
NoneNo data is disclosed.
Integrity
HighData or code can be modified at will.
Availability
HighThe component can be taken down completely.

Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:H. Scored by NVD.

Scoring systemScoreSeverityScored by
CVSS 4.08.4HighCNA (rockwellautomation.com)
CVSS 3.19.1CriticalNVD

Official description

A security issue exists within the FactoryTalk Linx Network Browser. By modifying the process.env.NODE_ENV to ‘development’, the attacker can disable FTSP token validation. This bypass allows access to create, update, and delete FTLinx drivers.

Source: the CVE record as published by its numbering authority, via NVD and CVE.org.

The underlying weakness: Incorrect User Management

The product does not properly manage a user within its environment.

More Incorrect User Management vulnerabilities (CWE-286)

Timeline

  1. CVE record published.
  2. CISA published its SSVC assessment (exploitation: none, automatable: no, technical impact: partial).
  3. Record last changed materially (score, affected products, status or references).

References

Other vulnerabilities in FactoryTalk® Linx

All FactoryTalk® Linx vulnerabilities

Recent Incorrect User Management vulnerabilities

Spotted an error? Tell us.