CyberSecBulletin
CVE-2022-26034NVD status: Modified

CENTUM VP series with VP6E5000(AD Suite…: Improper Authentication

CVE-2022-26034 is a critical-severity improper authentication vulnerability in CENTUM VP series with VP6E5000(AD Suite Engineering ServerFunction) installed and B/M9000 VP from Yokogawa Electric, with a CVSS 3.1 base score of 9.1 out of 10. It can be exploited remotely over the network by an unauthenticated attacker, without any action from a user. There is no confirmed exploitation so far. EPSS estimates a 0.98% chance of exploitation within 30 days, higher than 63% of scored CVEs.

Patch this week

Critical severity: a successful attack would have severe impact.

What to do

  1. Check which version of CENTUM VP series with VP6E5000(AD Suite Engineering ServerFunction) installed and B/M9000 VP you run against the affected versions below, and install the vendor's latest release.
  2. Read the advisory on yokogawa.com for workarounds and exact fixed builds.
  3. Until you can update, restrict network access to the affected service so it is not reachable from untrusted networks.

Affected products and versions

VendorProductAffected versionsFixed in
Yokogawa ElectricCENTUM VP series with VP6E5000(AD Suite Engineering ServerFunction) installed and B/M9000 VPNot specified in the recordNot stated
YokogawaB/m9000 Vpr8.01.01 through r8.03.01Not stated
YokogawaCentum Vpr6.01.10 through r6.09.00; r6.01.10 through r06.09.00Not stated

Version data comes from the organisation that assigned the CVE. Confirm against the vendor advisory before deciding you are unaffected.

How the severity score breaks down

Attack vector
NetworkCan be exploited remotely over a network, including the internet.
Attack complexity
LowNo special conditions are needed; the attack works reliably.
Privileges required
NoneNo account or login is needed.
User interaction
NoneNo action by a victim is required.
Scope
UnchangedImpact stays within the vulnerable component.
Confidentiality
HighAll data handled by the component can be read.
Integrity
HighData or code can be modified at will.
Availability
NoneAvailability is not affected.

Vector: CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N. Scored by NVD.

Scoring systemScoreSeverityScored by
CVSS 3.19.1CriticalNVD
CVSS 2.05.8MediumNVD

Official description

Improper authentication vulnerability in the communication protocol provided by AD (Automation Design) server of CENTUM VP R6.01.10 to R6.09.00, CENTUM VP Small R6.01.10 to R6.09.00, CENTUM VP Basic R6.01.10 to R6.09.00, and B/M9000 VP R8.01.01 to R8.03.01 allows an attacker to use the functions provided by AD server. This may lead to leakage or tampering of data managed by AD server.

Source: the CVE record as published by its numbering authority, via NVD and CVE.org.

The underlying weakness: Improper Authentication

When an actor claims to have a given identity, the product does not prove or insufficiently proves that the claim is correct.

How developers prevent this class of flaw

  • Use an authentication framework or library such as the OWASP ESAPI Authentication feature.

More Improper Authentication vulnerabilities (CWE-287)

Timeline

  1. CVE record published.
  2. Record last changed materially (score, affected products, status or references).

References

Third-party and government advisories

Recent Improper Authentication vulnerabilities

Spotted an error? Tell us.