Yokogawa vulnerabilities
We track 19 vulnerabilities in Yokogawa products across 18 products. 19 are rated high or critical, and none are known to be exploited. The most recent was published on September 17, 2024.
Latest Yokogawa vulnerabilities
- 7.5 High severity
Dual-redundant Platform for Computer (PC2CKM): Unchecked Return Value
Denial of Service (DoS) vulnerability has been found in Dual-redundant Platform for Computer. If a computer on which the affected product is installed receives a large number of UDP broadcast packets in a short period, occasionally that computer may restart. I
- 8.5 High severity
CENTUM CS 3000: Improper Access Control
DLL Hijacking vulnerability has been found in CENTUM CAMS Log server provided by Yokogawa Electric Corporation. If an attacker is somehow able to intrude into a computer that installed affected product or access to a shared folder, by replacing the DLL file wi
- 7.8 High severity
CENTUM series: Cleartext Storage of Sensitive Information
CENTUM series provided by Yokogawa Electric Corporation are vulnerable to cleartext storage of sensitive information. If an attacker who can login or access the computer where the affected product is installed tampers the password file stored in the computer,
- 9.8 Critical severity
WTViewerE series: Out-of-bounds Write
Stack-based buffer overflow in WTViewerE series WTViewerE 761941 from 1.31 to 1.61 and WTViewerEfree from 1.01 to 1.52 allows an attacker to cause the product to crash by processing a long file name.
- 7.5 High severity
Communication Module for Wide Area…: Use of Insufficiently Random Values
Use of insufficiently random values vulnerability exists in Vnet/IP communication module VI461 of YOKOGAWA Wide Area Communication Router (WAC Router) AW810D, which may allow a remote attacker to cause denial-of-service (DoS) condition by sending a specially c
- 7.2 High severity
STARDOM Controller: Use of Hard-coded Credentials
Use of hard-coded credentials vulnerability exists in STARDOM FCN Controller and FCJ Controller R4.10 to R4.31, which may allow an attacker with an administrative privilege to read/change configuration settings or update the controller with tampered firmware.
- 7.5 High severity
STARDOM Controller: Cleartext Transmission of Sensitive Information
Cleartext transmission of sensitive information vulnerability exists in STARDOM FCN Controller and FCJ Controller R1.01 to R4.31, which may allow an adjacent attacker to login the affected products and alter device configuration settings or tamper with device
- 7.8 High severity
CENTUM VP series with VP6E5150(Graphic…: Improper Neutralization of Special Elements used in an OS Command
OS command injection vulnerability exists in CENTUM VP R4.01.00 to R4.03.00, CENTUM VP Small R4.01.00 to R4.03.00, CENTUM VP Basic R4.01.00 to R4.03.00, and B/M9000 VP R6.01.01 to R6.03.02, which may allow an attacker who can access the computer where the affe
- 9.1 Critical severity
CENTUM VP series with VP6E5000(AD Suite…: Improper Authentication
Improper authentication vulnerability in the communication protocol provided by AD (Automation Design) server of CENTUM VP R6.01.10 to R6.09.00, CENTUM VP Small R6.01.10 to R6.09.00, CENTUM VP Basic R6.01.10 to R6.09.00, and B/M9000 VP R8.01.01 to R8.03.01 all
- 9.8 Critical severity
CENTUM VP: Use of Hard-coded Credentials
The following Yokogawa Electric products hard-code the password for CAMS server applications: CENTUM VP versions from R5.01.00 to R5.04.20 and versions from R6.01.00 to R6.08.00, Exaopc versions from R3.72.00 to R3.79.00
- 7.8 High severity
CENTUM CS 3000: Uncontrolled Search Path Element
The following Yokogawa Electric products contain insecure DLL loading issues. CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.01.00 to R4.03.00, from R5.01.00 to R5.04.20, and from R6.01.00 to R6.08.00, Exaopc versions from R3.72.
- 8.8 High severity
CENTUM CS 3000: Improper Authentication
CAMS for HIS Server contained in the following Yokogawa Electric products improperly authenticate the receiving packets. The authentication may be bypassed via some crafted packets: CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.
- 8.1 High severity
CENTUM CS 3000: Improper Encoding or Escaping of Output
CAMS for HIS Log Server contained in the following Yokogawa Electric products fails to properly neutralize log outputs: CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.01.00 to R4.03.00, from R5.01.00 to R5.04.20, and from R6.01.0
- 7.8 High severity
CENTUM CS 3000: Incorrect Permission Assignment for Critical Resource
'Root Service' service implemented in the following Yokogawa Electric products creates some named pipe with improper ACL configuration. CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.01.00 to R4.03.00, from R5.01.00 to R5.04.20,
- 8.1 High severity
CENTUM CS 3000: Uncontrolled Resource Consumption
CAMS for HIS Log Server contained in the following Yokogawa Electric products is vulnerable to uncontrolled resource consumption. CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.01.00 to R4.03.00, from R5.01.00 to R5.04.20, from R
- 7.8 High severity
CENTUM CS 3000: Improper Privilege Management
'Long-term Data Archive Package' service implemented in the following Yokogawa Electric products creates some named pipe with imporper ACL configuration. CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.01.00 to R4.03.00, from R5.0
- 8.8 High severity
CENTUM CS 3000: Improper Limitation of a Pathname to a Restricted Directory
Path traversal vulnerability exists in CAMS for HIS Server contained in the following Yokogawa Electric products: CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.01.00 to R4.03.00, from R5.01.00 to R5.04.20, and from R6.01.00 to R
- 9.8 Critical severity
CENTUM VP: Use of Hard-coded Credentials
The following Yokogawa Electric products do not change the passwords of the internal Windows accounts from the initial configuration: CENTUM VP versions from R5.01.00 to R5.04.20 and versions from R6.01.00 to R6.08.0, Exaopc versions from R3.72.00 to R3.79.00.
- 8.1 High severity
CENTUM CS 3000: Improper Limitation of a Pathname to a Restricted Directory
There is a path traversal vulnerability in CAMS for HIS Log Server contained in the following Yokogawa Electric products: CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.01.00 to R4.03.00, from R5.01.00 to R5.04.20, andfrom R6.01.