Centum Cs 3000 Entry Firmware vulnerabilities
8 known vulnerabilities in Centum Cs 3000 Entry Firmware from Yokogawa. 8 are rated high or critical. Each entry lists the affected versions and the release that fixes it, where the vendor has published one.
Latest first
- 7.8 High severity
CENTUM CS 3000: Uncontrolled Search Path Element
The following Yokogawa Electric products contain insecure DLL loading issues. CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.01.00 to R4.03.00, from R5.01.00 to R5.04.20, and from R6.01.00 to R6.08.00, Exaopc versions from R3.72.
- 8.8 High severity
CENTUM CS 3000: Improper Authentication
CAMS for HIS Server contained in the following Yokogawa Electric products improperly authenticate the receiving packets. The authentication may be bypassed via some crafted packets: CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.
- 8.1 High severity
CENTUM CS 3000: Improper Encoding or Escaping of Output
CAMS for HIS Log Server contained in the following Yokogawa Electric products fails to properly neutralize log outputs: CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.01.00 to R4.03.00, from R5.01.00 to R5.04.20, and from R6.01.0
- 7.8 High severity
CENTUM CS 3000: Incorrect Permission Assignment for Critical Resource
'Root Service' service implemented in the following Yokogawa Electric products creates some named pipe with improper ACL configuration. CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.01.00 to R4.03.00, from R5.01.00 to R5.04.20,
- 8.1 High severity
CENTUM CS 3000: Uncontrolled Resource Consumption
CAMS for HIS Log Server contained in the following Yokogawa Electric products is vulnerable to uncontrolled resource consumption. CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.01.00 to R4.03.00, from R5.01.00 to R5.04.20, from R
- 7.8 High severity
CENTUM CS 3000: Improper Privilege Management
'Long-term Data Archive Package' service implemented in the following Yokogawa Electric products creates some named pipe with imporper ACL configuration. CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.01.00 to R4.03.00, from R5.0
- 8.8 High severity
CENTUM CS 3000: Improper Limitation of a Pathname to a Restricted Directory
Path traversal vulnerability exists in CAMS for HIS Server contained in the following Yokogawa Electric products: CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.01.00 to R4.03.00, from R5.01.00 to R5.04.20, and from R6.01.00 to R
- 8.1 High severity
CENTUM CS 3000: Improper Limitation of a Pathname to a Restricted Directory
There is a path traversal vulnerability in CAMS for HIS Log Server contained in the following Yokogawa Electric products: CENTUM CS 3000 versions from R3.08.10 to R3.09.00, CENTUM VP versions from R4.01.00 to R4.03.00, from R5.01.00 to R5.04.20, andfrom R6.01.