CVE-2022-30319NVD status: Modified

Saia Pg5 Controls Suite: Authentication Bypass by Spoofing

CVE-2022-30319 is a high-severity authentication bypass by spoofing vulnerability in Saia Pg5 Controls Suite from Honeywell, with a CVSS 3.1 base score of 8.1 out of 10. It can be exploited from the same local network by an unauthenticated attacker, without any action from a user. There is no confirmed exploitation so far. EPSS estimates a 0.7% chance of exploitation within 30 days, higher than 54% of scored CVEs.

Next patch cycle

High severity with no evidence of exploitation so far.

What to do

  1. Check which version of Saia Pg5 Controls Suite you run against the affected versions below, and install the vendor's latest release.

Affected products and versions

VendorProductAffected versionsFixed in
HoneywellSaia Pg5 Controls SuiteNot specified in the recordNot stated

Version data comes from NVD's product matching. Confirm against the vendor advisory before deciding you are unaffected.

How the severity score breaks down

Attack vector
AdjacentThe attacker must be on the same local network segment.
Attack complexity
LowNo special conditions are needed; the attack works reliably.
Privileges required
NoneNo account or login is needed.
User interaction
NoneNo action by a victim is required.
Scope
UnchangedImpact stays within the vulnerable component.
Confidentiality
HighAll data handled by the component can be read.
Integrity
HighData or code can be modified at will.
Availability
NoneAvailability is not affected.

Vector: CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N. Scored by NVD.

Official description

Saia Burgess Controls (SBC) PCD through 2022-05-06 allows Authentication bypass. According to FSCT-2022-0062, there is a Saia Burgess Controls (SBC) PCD S-Bus authentication bypass issue. The affected components are characterized as: S-Bus (5050/UDP) authentication. The potential impact is: Authentication bypass. The Saia Burgess Controls (SBC) PCD controllers utilize the S-Bus protocol (5050/UDP) for a variety of engineering purposes. It is possible to configure a password in order to restrict access to sensitive engineering functionality. Authentication functions on the basis of a MAC/IP whitelist with inactivity timeout to which an authenticated client's MAC/IP is stored. UDP traffic can be spoofed to bypass the whitelist-based access control. Since UDP is stateless, an attacker capable of passively observing traffic can spoof arbitrary messages using the MAC/IP of an authenticated client. This allows the attacker access to sensitive engineering functionality such as uploading/downloading control logic and manipulating controller configuration.

Source: the CVE record as published by its numbering authority, via NVD and CVE.org.

The underlying weakness: Authentication Bypass by Spoofing

This attack-focused weakness is caused by incorrectly implemented authentication schemes that are subject to spoofing attacks.

More Authentication Bypass by Spoofing vulnerabilities (CWE-290)

Timeline

  1. CVE record published.
  2. CISA published its SSVC assessment (exploitation: none, automatable: no, technical impact: total).