CyberSecBulletin
CVE-2023-5393NVD status: Deferred

Experion Server: Improper Handling of Length Parameter Inconsistency

CVE-2023-5393 is a high-severity improper handling of length parameter inconsistency vulnerability in Experion Server from Honeywell, with a CVSS 3.1 base score of 7.4 out of 10. It can be exploited remotely over the network by an unauthenticated attacker, without any action from a user. Affected Experion Server versions: 520.2 through 520.2 TCU4; 511.1 through 511.5 TCU4 HF3; 520.1 through 520.1 TCU4, and others listed below. The record does not name a fixed version, so check the vendor advisory. There is no confirmed exploitation so far. EPSS estimates a 0.71% chance of exploitation within 30 days, higher than 54% of scored CVEs.

Next patch cycle

High severity with no evidence of exploitation so far.

What to do

  1. Check which version of Experion Server you run against the affected versions below, and install the vendor's latest release.
  2. Until you can update, restrict network access to the affected service so it is not reachable from untrusted networks.

Affected products and versions

VendorProductAffected versionsFixed in
HoneywellExperion Server520.2 through 520.2 TCU4; 511.1 through 511.5 TCU4 HF3; 520.1 through 520.1 TCU4; 520.2 TCU4 HFR2 through 511.5 TCU4 HF3Not stated

Version data comes from the organisation that assigned the CVE. Confirm against the vendor advisory before deciding you are unaffected.

How the severity score breaks down

Attack vector
NetworkCan be exploited remotely over a network, including the internet.
Attack complexity
HighSuccess depends on conditions outside the attacker's control.
Privileges required
NoneNo account or login is needed.
User interaction
NoneNo action by a victim is required.
Scope
UnchangedImpact stays within the vulnerable component.
Confidentiality
NoneNo data is disclosed.
Integrity
HighData or code can be modified at will.
Availability
HighThe component can be taken down completely.

Vector: CVSS:3.1/AV:N/AC:H/PR:N/UI:N/S:U/C:N/I:H/A:H. Scored by CNA (honeywell.com).

Official description

Server receiving a malformed message that causes a disconnect to a hostname may causing a stack overflow resulting in possible remote code execution. Honeywell recommends updating to the most recent version of the product. See Honeywell Security Notification for recommendations on upgrading and versioning.

Source: the CVE record as published by its numbering authority, via NVD and CVE.org.

The underlying weakness: Improper Handling of Length Parameter Inconsistency

The product parses a formatted message or structure, but it does not handle or incorrectly handles a length field that is inconsistent with the actual length of the associated data.

How developers prevent this class of flaw

  • When processing structured incoming data containing a size field followed by raw data, ensure that you identify and resolve any inconsistencies between the size field and the actual size of the data.
  • Do not let the user control the size of the buffer.
  • Validate that the length of the user-supplied data is consistent with the buffer size.

More Improper Handling of Length Parameter Inconsistency vulnerabilities (CWE-130)

Timeline

  1. CVE record published.
  2. CISA published its SSVC assessment (exploitation: none, automatable: no, technical impact: partial).
  3. Record last changed materially (score, affected products, status or references).

References

Other references

Other vulnerabilities in Experion Server

All Experion Server vulnerabilities

Recent Improper Handling of Length Parameter Inconsistency vulnerabilities

Spotted an error? Tell us.