CyberSecBulletin
CVE-2025-23365NVD status: Analyzed

TIA Administrator: Improper Access Control

CVE-2025-23365 is a high-severity improper access control vulnerability in TIA Administrator from Siemens, with a CVSS 3.1 base score of 7.8 out of 10. It can be exploited with local access to the system by an attacker with a low-privileged account, without any action from a user. The record lists version V3.0.6 as the first without the flaw, so updating TIA Administrator to that release or later removes the exposure. There is no confirmed exploitation so far. EPSS estimates a 0.15% chance of exploitation within 30 days, which is low compared with other CVEs.

Next patch cycle

High severity with no evidence of exploitation so far.

What to do

  1. Update TIA Administrator to V3.0.6 or a later version.
  2. Read the advisory on cert-portal.siemens.com for workarounds and exact fixed builds.

Affected products and versions

VendorProductAffected versionsFixed in
SiemensTIA Administratorbefore V3.0.6V3.0.6

Version data comes from the organisation that assigned the CVE. Confirm against the vendor advisory before deciding you are unaffected.

How the severity score breaks down

Attack vector
LocalThe attacker needs local access or must trick a user into running something.
Attack complexity
LowNo special conditions are needed; the attack works reliably.
Privileges required
LowA basic user account is enough.
User interaction
NoneNo action by a victim is required.
Scope
UnchangedImpact stays within the vulnerable component.
Confidentiality
HighAll data handled by the component can be read.
Integrity
HighData or code can be modified at will.
Availability
HighThe component can be taken down completely.

Vector: CVSS:3.1/AV:L/AC:L/PR:L/UI:N/S:U/C:H/I:H/A:H. Scored by CNA (siemens.com).

Scoring systemScoreSeverityScored by
CVSS 4.08.5HighCNA (siemens.com)
CVSS 3.17.8HighCNA (siemens.com)

Official description

A vulnerability has been identified in TIA Administrator (All versions < V3.0.6). The affected application allows low-privileged users to trigger installations by overwriting cache files and modifying the downloads path. This would allow an attacker to escalate privilege and exceute arbitrary code.

Source: the CVE record as published by its numbering authority, via NVD and CVE.org.

The underlying weakness: Improper Access Control

The product does not restrict or incorrectly restricts access to a resource from an unauthorized actor.

How developers prevent this class of flaw

  • Very carefully manage the setting, management, and handling of privileges. Explicitly manage trust zones in the software.
  • Compartmentalize the system to have safe areas where trust boundaries can be unambiguously drawn. Do not allow sensitive data to go outside of the trust boundary and always be careful when interfacing with a compartment outside of the safe area. Ensure that appropriate compartmentalization is built into the system design, and the compartmentalization allows for and reinforces privilege separation functionality. Architects and designers should rely on the principle of least privilege to decide the appropriate time to use privileges and the time to drop privileges.

More Improper Access Control vulnerabilities (CWE-284)

Timeline

  1. CVE record published.
  2. CISA published its SSVC assessment (exploitation: none, automatable: no, technical impact: total).
  3. Record last changed materially (score, affected products, status or references).

References

Other vulnerabilities in TIA Administrator

All TIA Administrator vulnerabilities

Recent Improper Access Control vulnerabilities

Spotted an error? Tell us.